(a) If the ground scanning gives the maintenance message: L SPLR 3 POS XDCR 31CE5
- refer to the Para. Fault Isolation.
(b) If the ground scanning gives the maintenance messages: L SPLR 3 POS XDCR 31CE5 R SPLR 3 POS XDCR 31CE6
- refer to this procedure (Ref. TASK 27-90-00-810-802).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞27-60-00∞∞∞∞∞∞∞∞∞∞Page 248
Nov 01/02 CES
4. Fault Isolation
_______________
A. If the BITE test gives the maintenance message: L SPLR 3 POS XDCR 31CE5:
- replace the SERVO CTL-SPLR3, L B (31CE5), (Ref. AMM TASK 27-64-51-000-001) and (Ref. AMM TASK 27-64-51-400-001).
NOTE : The resistance of primary and secondary windings must be between
____
30 ohms and 500 ohms.
(1) If the fault continues:
- do a check and repair the wiring of the POS XDCR SPLY signal from the servo control (31CE5) to the first terminal block, (Ref. ASM 27-94/02).
(2) If the fault continues:
- do a check and repair the wiring of the POS XDCR V1, V2 signals from the servo control (31CE5) to the first terminal block, (Ref. ASM 27-94/02).
B. Do the tests given in Para. 3.
Loss of the Left Spoiler 3 Position Signal for the SEC 1
1. Possible Causes
_______________
- SEC-1 (1CE1)
- wiring of the ANI 2-4 signal from the SEC 1 (1CE1) to the first terminal block
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 27-94-34-000-001 Removal of the SEC (1CE1,1CE2,1CE3)
AMM 27-94-34-400-001 Installation of the SEC (1CE1,1CE2,1CE3)
AMM 27-96-00-710-020 Operational Test of the Side Stick Assembly
(Activation for the BITE Test) R AMM 27-96-00-740-001 BITE Test of the EFCS (Ground Scanning) ASM 27-94/02
3. Fault Confirmation
__________________
A. Test
(1) Do the operational test of the side stick assembly (activation for the BITE test) (Ref. AMM TASK 27-96-00-710-020).
(2) Do the BITE test of the EFCS (Ground Scanning) (Ref. AMM TASK 27-96-00-740-001).
4. Fault Isolation
_______________
A. If the BITE test gives the maintenance message:
SEC1 COM OR WIRING FROM L SPLR3 POS XDCR 31CE5
or
SEC1 MON OR WIRING FROM L SPLR3 POS XDCR 31CE5
- replace the SEC-1 (1CE1), (Ref. AMM TASK 27-94-34-000-001) and (Ref. AMM TASK 27-94-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring of the ANI 2-4 signal from the SEC 1 (1CE1) to the first terminal block COM part or MON part as shown in the maintenance message (Ref. ASM 27-94/02).
B. Do the tests given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞27-60-00∞∞∞∞∞∞∞∞∞∞Page 250
May 01/00 CES Loss of the Right Spoiler 3 Position Signal for the SEC 1
1. Possible Causes
_______________
- SEC-1 (1CE1)
- wiring of the ANI 2-5 signal from the SEC 1 (1CE1) to the first terminal block
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 27-94-34-000-001 Removal of the SEC (1CE1,1CE2,1CE3)
AMM 27-94-34-400-001 Installation of the SEC (1CE1,1CE2,1CE3)
AMM 27-96-00-710-020 Operational Test of the Side Stick Assembly
(Activation for the BITE Test) R AMM 27-96-00-740-001 BITE Test of the EFCS (Ground Scanning) ASM 27-94/02
3. Fault Confirmation
__________________
A. Test
(1) Do the operational test of the side stick assembly (activation for the BITE test) (Ref. AMM TASK 27-96-00-710-020).
(2) Do the BITE test of the EFCS (Ground Scanning) (Ref. AMM TASK 27-96-00-740-001).
4. Fault Isolation
_______________
A. If the BITE test gives the maintenance message:
SEC1 COM OR WIRING FROM R SPLR3 POS XDCR 31CE6
or
SEC1 MON OR WIRING FROM R SPLR3 POS XDCR 31CE6