1 If the resistance values are out of the specified limits:
_ a Replace the solenoid valve of the servocontrol 34CE3 (Ref.
_ AMM TASK 27-34-51-000-005) and (Ref. AMM TASK 27-34-51-400-004).
b Do again a check of the resistance of the solenoid valve
_ between the pin C/J and the pin C/U of the outboard elevator servocontrol (34CE3) (40 to 100 Ohms).
- If the resistance values are out of the specified limits: . Replace the SERVO CTL-L ELEVATOR, OUTBD B (34CE3) (Ref. AMM TASK 27-34-51-000-001) and (Ref. AMM TASK 27-34-51-400-001). . Install the SEC2 (Ref. AMM TASK 27-94-34-400-001).
- If the resistance values are in the specified limits: Install the SEC2 (Ref. AMM TASK 27-94-34-400-001).
2 If the resistance values are in the specified limits:
_ a Repair the wiring of the SOL VLV2 signal from the
_ servocontrol (34CE3) to the SEC2 (1CE2), from the pin C/J to the pin AB/14D and from the pin C/U to the pin AE/14G (Ref. ASM 27-94/08):
b Install the SEC2 (Ref. AMM TASK 27-94-34-400-001).
_
(c) If the resistance values are in the specified limits: R - See Para. (3).
R (3) At the SEC2 receptacle, do a check of the insulation between pin R AE/14G (pin AB/14D) and the ground.
R NOTE : The resistance must be more than 100 Meghoms.
____
R (a) If the resistance is more than 100 Megohms:
R - Replace the SEC-2 (1CE2) (Ref. AMM TASK 27-94-34-000-001) and
R (Ref. AMM TASK 27-94-34-400-001).
R 1_ If the fault continues:
R - Replace the solenoid valve (Ref. AMM TASK 27-34-51-000-005)
R and (Ref. AMM TASK 27-34-51-400-004).
R 2_ If the fault continues:
R - Replace the SERVO CTL-L ELEVATOR, OUTBD B (34CE3) (Ref. AMM
R TASK 27-34-51-000-001) and (Ref. AMM TASK 27-34-51-400-001).
R
R 3_ do a check of the wiring from the SEC2 (1CE2) COM part to theR SEC2 MON part, from the pin AB/11F to the pin AE/14E (Ref. ASM 27-94/08):
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞27-30-00∞∞∞∞∞∞∞∞∞∞Page 221
Aug 01/00 CES
R
R a_ If the wiring is correct:
- replace the SEC-2 (1CE2) (Ref. AMM TASK 27-94-34-000-001)
and (Ref. AMM TASK 27-94-34-400-001).
R
R b_ If the wiring is not correct:
- repair it
- install the SEC2 (Ref. AMM TASK 27-94-34-400-001).
R
R (b) If the resistance is less than 100 Meghoms:
R - At the SERVO CTL-L ELEVATOR, OUTBD B (34CE3), do a check of the
R insulation between pin C/U (pin C/J) and the ground.
R 1_ If the resistance is less than 100 Megohms:
R - Replace the solenoid valve (Ref. AMM TASK 27-34-51-000-005)
R and (Ref. AMM TASK 27-34-51-400-004).
R a_ Do again a check of the insulation of the solenoid valve
R between pin C/U (pin C/J) and the ground.
R - If the resistance is less than 100 Megohms:
R . Replace the SERVO CTL-L ELEVATOR, OUTBD B (34CE3) (Ref.
R AMM TASK 27-34-51-000-001) and (Ref. AMM TASK 27-34-51-
400-001).
R . Replace the SEC-2 (1CE2) (Ref. AMM TASK 27-94-34-000-
R 001) and (Ref. AMM TASK 27-94-34-400-001).
R 2_ If the resistance is more than 100 Meghoms:
R a_ Repair the wiring of the solenoid valve signal from the
R SERVO CTL-L ELEVATOR, OUTBD B (34CE3) to the SEC-2 (1CE2).
R b_ Replace the SEC-2 (1CE2) (Ref. AMM TASK 27-94-34-000-001)
R and (Ref. AMM TASK 27-94-34-400-001).
B. Do the tests given in Para. 3.
Failure of the Left Green Elevator-Servocontrol Position-Transducer
1. Possible Causes
_______________
- SERVO CTL-L ELEVATOR, INBD G (34CE1)
- wiring of the POS XDCR COM SPLY signal from the servocontrol (34CE1) to the first terminal block
- wiring of the POS XDCR COM V1, V2 signals from the servocontrol (34CE1) to the first terminal block 中国航空网 www.aero.cn 航空翻译 www.aviation.cn 本文链接地址:A320 Trouble Shooting Manual 排故手册 飞行操纵 1(44)