The manual system test and the power-up mode will not invalidate an alarm in progress. Neither test will cause the APU to shutdown.


 D. Control
_______
 (1)  Turn-on procedure:
 (a)  
Provide electrical power (AMM 24-22-00).

 (b)  
Check that the following circuit breakers on overhead circuit breaker panel P11 are closed: 1) FIRE DET ALTN PWR APU 2) FIRE DETECTION APU 1 and 2 3) APU REMOTE FIRE IND


 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-15-00
 ALL  ú ú 02 Page 11 ú Jan 28/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
757 FAULT ISOLATION/MAINT MANUAL
APU FIRE DETECTION SYSTEM
COMPONENT SHT 102 FIG.  QTY  ACCESS/AREA  REFERENCE AMM 
CARD 3 - FIRE/OVHT LOGIC/TEST, M10400  2  1  119BL, MAIN EQUIP CTR, P54  26-10-01 
CARD - LOOP 1 APU FIRE DET, M685  2  1  119BL, MAIN EQUIP CTR, P54  26-10-01 
CARD - LOOP 2 APU FIRE DET, M686  2  1  119BL, MAIN EQUIP CTR, P54  26-10-01 
CARD - L ENG SPEED, M10298  2  1  119BL, MAIN EQUIP CTR, P50  * 
CARD - R ENG SPEED, M10311  2  1  119BL, MAIN EQUIP CTR, P50  * 
CIRCUIT BREAKER - 1 FLT COMPT, P11 
APU REMOTE FIRE IND, C796 1  11B33 * 
FIRE DET ALTN PWR APU, C765  1  11J25  * 
FIRE DETECTION APU 1, C776  1  11B24  * 
EICAS R, M10182 EICAS L, M10181 FIRE DETECTION APU 2, C785COMPUTER - (FIM 31-41-00/101)  1  11B25  * 
TS5063 DETECTOR - APU FIRE, TS5066,TS5067,TS5062, 2  2  315AL,316AR, APU COMPT  26-15-02 
DIODE - BUS ISOLATION, R201,R202  1  2  FLT COMPT, BEHIND P5  * 
DIODE - ISOLATION 1, R10088  1 FLT COMPT, BEHIND P36 
HORN - APU FIRE WARNING, B122 1  NOSE LANDING GEAR, P62  * 
LIGHT - APU FIRE, L401  1  NOSE LANDING GEAR, P62  * 
AIR GND, K145 APU FIRE, K10334 APU GND, K10373 MODULE - DISCRETE WARNING DISPLAY, M779 APU/CARGO FIRE CONT, M10444 FIRE/OVHT TEST, M10445 PANEL - (FIM 26-11-00/101) PANEL - (FIM 26-22-00/101) PANEL - (FIM 49-61-00/101) APU START, M10324 OR APU CONTROL, M1 APU HORN INTERRUPTER, K420 TEST, K10325 APU REMOTE WARNING, K10374 AIR GND SYS 2, K219 EXTERNAL SHUTDOWN, K421 RELAY - (FIM 31-01-33/101) RELAY - (FIM 31-01-36/101) RELAY - (FIM 31-01-37/101)  1  1  FLT COMPT, P1-3  * 
SWITCH - APU BOTTLE DISCH, S485  1  1  NOSE LANDING GEAR, P62  * 
SWITCH - APU FIRE, S39  1  1  FLT COMPT, P8, APU/CARGO FIRE  * 
CONTROL PANEL, M10444 
SWITCH - APU FIRE SHUTDOWN, S484  1  1  NOSE LANDING GEAR, P62  * 
SWITCH - ENG/APU/CARGO, YQQS001  1  1  FLT COMPT, P8, FIRE/OVHT TEST * 
PANEL, M10445 
SWITCH - FAIL LIGHT RESET, YQQS002 1 1  FLT COMPT, P8, FIRE/OVHT TEST * 
PANEL, M10445 

* SEE THE WDM EQUIPMENT LIST
APU Fire Detection System - Component Index
Figure 101

EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-15-00
 ALL  ú
 ú  06  Page 101
 ú  Jun 20/95 

BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
757 FAULT ISOLATION/MAINT MANUAL
DISCRETE WARNING
SWITCH, YQQ S001

B

FIRE
LIGHT


FIRE
CONFIG
R
R
A/P
PULLUP
R
DISC R
CABIN
OVSPD
R
ALT R

APU Fire Detection System - Component Location
Figure 102 (Sheet 1)

EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-15-00
 ALL  ú
 ú  01  Page 102
 ú  Jun 20/95 

BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
 
中国航空网 www.aero.cn
航空翻译 www.aviation.cn
本文链接地址:757 AMM 飞机维护手册 防火 FIRE PROTECTION 1(62)