R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
B. Test
Do the EIS input test (Ref. AMM TASK 31-60-00-740-002).
R **ON A/C 401-499,
B. Test Do the Ground Scanning Test of the DMC (Ref. AMM TASK 31-60-00-740-007).
**ON A/C ALL
4. Fault Isolation
_______________
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
A. If the test gives the maintenance message DMC 2 : NO ILS 2 DATA:
- replace the DMC-2 (1WT2) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the DMC 2 (1WT2) pins AA/6J, 6K to the first terminal block (Ref. ASM 31-62/01).
R **ON A/C 401-499,
A. If the test gives the maintenance message ILS2(40RT2)/DMC2(1WT2) or MMR2(40RT2)/DMC2(1WT2):
- replace the DMC-2 (1WT2) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the ILS2/MMR2(40RT2) pins AB-1G/1H to the DMC2(1WT2) pins AA-10J/10K (Ref. ASM 31-62/01).
(2) If the fault continues:
- replace the ILS2(40RT2) (Ref. AMM TASK 34-36-31-000-003) and (Ref. AMM TASK 34-36-31-400-003), or the MMR2(40RT2) (Ref. AMM TASK 34-36-31-000-002) and (Ref. AMM TASK 34-36-31-400-002).
**ON A/C ALL
B. Do the test given in Para. 3.B.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-63-00∞∞∞∞∞∞∞∞∞∞Page 282
Aug 01/05 CES Loss of the IRS 2 Output Bus by the DMC 2
1. Possible Causes
_______________
- DMC-2 (1WT2)
- ADIRU-2 (1FP2)
- wiring from the ADIRU 2 (1FP2) to the DMC 2 (1WT2)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 31-60-00-740-002 EIS Input Test
AMM 31-60-00-740-007 GROUND SCANNING Test of the DMC
AMM 31-63-34-000-001 Removal of the DMC (1WT1,1WT2,1WT3)
AMM 31-63-34-400-001 Installation of the DMC (1WT1,1WT2,1WT3)
AMM 34-12-34-000-001 Removal of the ADIRU (1FP1, 1FP2, 1FP3)
AMM 34-12-34-400-001 Installation of the ADIRU (1FP1, 1FP2, 1FP3)
ASM 31-62/01
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
**ON A/C 001-049, 051-061, 101-105, 201-203,
121VU ADIRS/ADIRU/2PWR/SHED 10FP N11 121VU ADIRS/ADIRU/2/26VAC AND AOA 5FP2 N09 121VU ADIRS/ADIRU/2/115VAC 4FP2 N07 121VU ADIRS/ADIRU/2/28VDC 6FP2 N05
R **ON A/C 062-099, 106-149, 151-199, 204-299, 301-399, 401-499,
121VU ADIRS/ADIRU/2PWR/SHED 10FP N10 121VU ADIRS/ADIRU/2/26VAC AND AOA 5FP2 N08 121VU ADIRS/ADIRU/2/115VAC 4FP2 N06 121VU ADIRS/ADIRU/2/28VDC 6FP2 N04
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-63-00∞∞∞∞∞∞∞∞∞∞Page 283
Aug 01/05 CES
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
B. Test
Do the EIS input test (Ref. AMM TASK 31-60-00-740-002).
R **ON A/C 401-499,
B. Test Do the Ground Scanning Test of the DMC (Ref. AMM TASK 31-60-00-740-007).
**ON A/C ALL
4. Fault Isolation