4. Fault Isolation
_______________
A. If the test gives the maintenance message SDAC 2 : NO DATA FROM ECS 1+2:
- replace the SDAC-2 (1WV2) (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).
(1) If the fault continues:
- do a check and repair as necessary the wiring from the SDAC 2 (1WV2) . pins AB/14J, 14K to the first terminal block . pins AE/14A, 14B to the first terminal block (Ref. ASM 31-54/03).
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-54-00∞∞∞∞∞∞∞∞∞∞Page A258
Aug 01/05R
CES Loss of the SFCC 1 and SFCC 2 Buses of the SDAC 1
1. Possible Causes
_______________
- SDAC-1 (1WV1)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 31-50-00-710-001 Ground Scanning of the Central Warning System
AMM 31-55-34-000-001 Removal of the SDAC (1WV1,1WV2)
AMM 31-55-34-400-001 Installation of the SDAC (1WV1,1WV2)
ASM 31-54/03
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------49VU FLIGHT CONTROLS/SLT FLP/POS/IND 1 1CN B12 49VU FLIGHT CONTROLS/FLP/CTL AND MONG/SYS1 6CV B07 49VU FLIGHT CONTROLS/SLT/CTL AND MONG/SYS1 5CV B06 105VU ELEC/HOT BUS/702PP SPLY 5PB2 D02 105VU ELEC/HOT BUS/701PP SPLY 5PB1 D01 105VU ELEC/HOT BUS/702PP SPLY 12PB2 E02 105VU ELEC/HOT BUS/701PP SPLY 12PB1 E01 121VU FLIGHT CONTROLS/SLT FLP/POS/IND2 2CN P16 121VU FLIGHT CONTROLS/FLP/CTL AND/MONG/SYS2 8CV Q21 121VU FLIGHT CONTROLS/SLT/CTL/SYS2 7CV R21
B. Test Do the operational test of the central warning systems (SDAC) (Ref. AMM TASK 31-50-00-710-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-54-00∞∞∞∞∞∞∞∞∞∞Page A259
Aug 01/05R
CES 4. Fault Isolation
_______________
A. If the test gives the maintenance message SDAC 1 : NO DATA FROM SFCC 1+2:
- replace the SDAC-1 (1WV1) (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).
(1) If the fault continues:
- do a check and repair as necessary the wiring from the SDAC 1 (1WV1) . pins AB/11J, 11K to the first terminal block . pins AE/11A, 11B to the first terminal block (Ref. ASM 31-54/03).
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-54-00∞∞∞∞∞∞∞∞∞∞Page A260
Aug 01/05R
CES Loss of the SFCC 1 and SFCC 2 Buses of the SDAC 2
1. Possible Causes
_______________
- SDAC-2 (1WV2)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 31-50-00-710-001 Ground Scanning of the Central Warning System
AMM 31-55-34-000-001 Removal of the SDAC (1WV1,1WV2)
AMM 31-55-34-400-001 Installation of the SDAC (1WV1,1WV2)
ASM 31-54/03
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------49VU FLIGHT CONTROLS/SLT FLP/POS/IND 1 1CN B12 49VU FLIGHT CONTROLS/FLP/CTL AND MONG/SYS1 6CV B07 49VU FLIGHT CONTROLS/SLT/CTL AND MONG/SYS1 5CV B06 121VU FLIGHT CONTROLS/WTB/FLP/SYS2 12CV P20 121VU FLIGHT CONTROLS/WTB/SLT/SYS2 11CV P19 121VU FLIGHT CONTROLS/SLT FLP/POS/IND2 2CN P16 121VU FLIGHT CONTROLS/FLP/CTL AND/MONG/SYS2 8CV Q21 121VU FLIGHT CONTROLS/SLT/CTL/SYS2 7CV R21 122VU FLIGHT CONTROLS/WTB/FLP/SYS1 10CV S07 122VU FLIGHT CONTROLS/WTB/SLT/SYS1 9CV S06