- CROSSLOAD IN PROGRESS 

January 1, 2004 - 71 -
737-700 MAINTENANCE TRAINING MANUAL
-CROSSLOAD COMPLETE -CROSSLOAD FAIL (the data base in the source FMC did not crossload to the target FMC) -CROSSLOAD UNAVAILABLE (the source FMC can not interface with the other FMC) -SET FMC SOURCE SELECT TO BOTH ON R (shows when the primary FMC is also the target FMC).
To start the crossload, select COPY FROM LEFT or COPY FROM RIGHT on the MCDU and push the EXEC key. The message CROSSLOAD IN PROGRESS shows during the crossload process. At the end of the crossload, the message CROSSLOAD COMPLETE shows on the MCDU.
Line select key 6L shows one of these prompts:
-INDEX (selects the FMCS BITE INDEX page) -CANCEL (shows when the source FMC for the crossload has been selected but the EXEC key has not been pressed) -NEXT MISMATCH.
The NEXT MISMATCH prompt shows either the specified ANALOG DISCRETE page if there is a discrete mismatch currently or the DATABASE CROSSLOAD page if there is not a discrete mismatch but there is a data base mismatch.
If there are no more mismatches between the FMCs, the INDEX prompt shows.
This line is blank while the crossload is in progress.
34-61

SOUTHWEST AIRLINES PROPRIETARY(c) All rights reserved
SOUTHWEST AIRLINES.
737-700 MAINTENANCE TRAINING MANUAL
FMCS - OFP CROSSLOAD PAGE
NOTE:  The example on the graphic shows a mismatch between the OFPs and also the position of the right ECS pack switch and a navigation data base mismatch between the FMCs.
January 1, 2004
34-61
- 72 -
SOUTHWEST AIRLINES PROPRIETARY(c) All rights reserved
SOUTHWEST AIRLINES.
737-700 MAINTENANCE TRAINING MANUAL

 


OR


OR

A34-61-00-076.fm
FMCS - OFP CROSSLOAD PAGE

January 1, 2004
34-61
- 73 -
SOUTHWEST AIRLINES PROPRIETARY(c) All rights reserved
SOUTHWEST AIRLINES.
FMCS - DATABASE CROSSLOAD PAGE
The database crossload page lets you review and, if necessary, transfer the various data bases between the FMCs.
These are the applicable data bases:
-Model/engine
-Navigation
-Performance defaults
-Software options.

This page shows for any of these conditions:
-During ground power-up, if there is a data base mismatch
between the primary and secondary FMCs -Data base with a different update version is loaded into one FMC -Selection of the CROSSLOAD prompt on the FMCS BITE INDEX
page if there is a data base mismatch.
NOTE:  The data base crossload page shows if there is not an OFP mismatch or an analog discrete mismatch between the FMCs. These have higher priority than the data base crossload pages.
Data Base Crossload Page Information
Lines 1L through 4L show the data fields for the individual data bases. If there are no mismatches, the data fields are blank.
 