Forward cargo fire switch is set to ARMED
*
Equipment cooling switch is set to OVRD
*
Ambient temperature (TAT) is more than 55F (13C)
*
Ground test commands the valve to close.
In the air, the forward cargo heat valve is open unless one of these conditions occurs:
*
Smoke is detected by the E/E cooling smoke detector
*
Forward cargo fire switch is set to ARMED
*
Equipment cooling switch is set to OVRD.
Normal Control -Vent Valve
The usual position of the vent valve changes so that its position is the opposite of the position of the heat valve. For example, when the heat valve is open the vent valve is closed.
21-27-00
Page 69 D633W101-BEJ Sep 05/2002
A/C -EQUIPMENT COOLING -FWD CGO HT & VENT VLVS -FUNCTIONAL DESCRIPTION
The vent valve and the cargo heat valve can both be close if the forward cargo fire switch is set to ARMED.
*
Smoke is detected by the E/E cooling smoke detector
*
Equipment cooling switch is set to OVRD.
Fail Safe Control
The relays that supply power to the valves are set so that they always supply power to close the valves. This makes sure both valves close if the right and left ECSMCs have malfunctions.
Indication
Status messages show when a valve has a malfunction or the circuit that controls the valves has a malfunction.
The ECSMCs monitor information from the ELMS. This information helps the ECSMCs isolate malfunctions with the valves.
EFFECTIVITY BEJ ALL 21-27-00
Page 70
D633W101-BEJ Sep 05/2002
A/C -EQUIPMENT COOLING -FWD CGO HT & VENT VLVS -FUNCTIONAL DESCRIPTION
EFFECTIVITY BEJ ALL 21-27-00
Page 71
D633W101-BEJ May 05/2002
A/C -EQUIPMENT COOLING -OPERATION
General
An equipment cooling switch lets you set the desired mode of operation for the equipment cooling system.
Automatic Operation
The equipment cooling switch is an alternate-action switch. AUTO shows when you push the switch. This selects automatic operation (normal mode of operation) of the equipment cooling.
The OVRD light comes on when the override valve is in the OVRD position. The system puts the valve in the override position automatically or when the switch is out (non-normal mode of operation). The override mode gives cooling above a sufficient cabin differential pressure when the airplane is above 25,000 feet (7625 meters).
The override mode removes power to the supply and vent fans and sets the override valve to the OVRD position. This lets air vent from the supply part of the system overboard through the override valve. See the OVERRIDE MODE page in this section for more information on the override mode.
Ground Operation
Operation of the system on the ground normally does not require any inputs from you except to make sure that AUTO is selected.
If ambient temperature is equal to or greater than 110F (43C), you must supply conditioned air to the airplane.
Training Information Point
You can operate the system on the ground with a malfunction of the vent fan as long as ambient temperature is below 86F (30C). If the temperature goes above 86F (30C), then you must supply conditioned air to the airplane.
EFFECTIVITY BEJ ALL 21-27-00
中国航空网 www.aero.cn
航空翻译 www.aviation.cn
本文链接地址:777 AMM 飞机维护手册 空调 Air Conditioning(30)