* Set the data loader selector to the CDU position
* Set the data loader 3-position switch to the CDU you will load
(the L position loads CDU 1 and the R position loads CDU 2)
* Open the data loader access door
* Put the CDU OPS software diskette into the ADL.
SHZ 001-003
This is a summary of the steps to load data with a PDL:
* Airplane must be on the ground
* Apply electrical power to the airplane
* Open the DATA LOADER circuit breaker on the P18-2 panel
* Connect the PDL to the data transfer receptacle
* Close the DATA LOADER circuit breaker
* Turn the PDL on
* Set the data loader selector to the CDU position
* Set the data loader 3-position switch to the CDU you will load
(the L position loads CDU 1 and the R position loads CDU 2)
* Open the data loader access door
* Put the CDU OPS software diskette into the PDL.
SHZ ALL
The CDUs show the DATA LOADER page when the CDU
receives valid data from the loader.
SHZ 009-999
The data load process is automatic. When the CDU shows the
message LOAD COMPLETE, remove the diskette from the ADL
and perform the applicable software verification procedure.
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
EFFECTIVITY
SHZ ALL 34-61-00
Page 98.113
D633A101-SHZ1 Oct 10/2003
BOEING PROPRIETARY - Copyright#- Unpublished Work - See title page for details.
737-600/700/800/900 AIRCRAFT MAINTENANCE MANUAL
34-61-00-092
SHZ 009-999 (Continued)
SHZ 001-003
The data load process is automatic. When the CDU shows the
message LOAD COMPLETE, remove the diskette from the PDL
and perform the applicable software verification procedure.
SHZ 009-999
Return the data loader selector to the NORM position after the
transfer is complete.
SHZ 001-003
Return the data loader selector to the NORM position after the
transfer is complete and disconnect the PDL from the data
transfer unit recepticle.
SHZ ALL
NOTE: Do not interrupt electrical power to the system during
software loading. If power is interrupted, you will need
to do the software load procedure again.
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
EFFECTIVITY
SHZ ALL 34-61-00
Page 98.114
D633A101-SHZ1 Oct 10/2003
BOEING PROPRIETARY - Copyright#- Unpublished Work - See title page for details.
737-600/700/800/900 AIRCRAFT MAINTENANCE MANUAL
34-61-00-092
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
EFFECTIVITY
SHZ 009-999 34-61-00
Page 98.115
D633A101-SHZ1 Oct 10/2003
BOEING PROPRIETARY - Copyright#- Unpublished Work - See title page for details.
737-600/700/800/900 AIRCRAFT MAINTENANCE MANUAL
34-61-00-092
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
EFFECTIVITY
SHZ 001-003 34-61-00
Page 98.116
D633A101-SHZ1 Oct 10/2003
BOEING PROPRIETARY - Copyright#- Unpublished Work - See title page for details.
737-600/700/800/900 AIRCRAFT MAINTENANCE MANUAL
34-61-00-092
THIS PAGE IS INTENTIONALLY LEFT BLANK
FMCS - TRAINING INFORMATION POINT - CDU DATA LOADING
34-61-00
Page 98.117
D633A101-SHZ1 Oct 10/2003
BOEING PROPRIETARY - Copyright#- Unpublished Work - See title page for details.
737-600/700/800/900 AIRCRAFT MAINTENANCE MANUAL
Load
After you put the diskette into the loader, the load process is
automatic. Except to change diskettes, no further operation is
necessary.
CURRENT RECORD shows the number of data base records
that are loaded into the FMC data base memory. TOTAL
RECORDS show the total number of records to be loaded into
the FMC data base memory.
During the loading process, the message LOAD IN PROGRESS
shows. INSERT NEXT DISK shows during multi-disk data base
load.
The load is complete when LOAD COMPLETE shows on the
CDU. Push the eject button on the loader to remove the diskette.
Load Failure Indications
If the loader finds a problem, a message shows on the data
loader display and DATA LOAD INOP shows on the CDUs.
If the FMC finds a problem with the data from the loader, the
CDU shows one of these messages:
* CHECK DBL OR INTERFACE (there is a problem that the
FMCS cannot isolate to the FMC or the loader)
* DB EXCEEDS FMC (the data on the disk is too large for FMC
memory)
* RESET COUNT EXCEEDED (five load attempts have failed)
* DB-OFP INCOMPATIBLE (the data on the disk does not
compare with the FMC operational program)
* CHECK MEDIA (part of the data on the disk cannot be read
by the loader)
 